10
2.
Controls (cont’d)
2.3 Deco-Touch Main Control (cont’d)
HOW TO SET THE RELATIVE HUMIDITY (RH) LEVEL AND CHOOSE BETWEEN
OFF IN STANDBY OR RECIRCULATION IN STAND-BY
SETTING THE RELATIVE HUMIDITY LEVEL ALLOWS TO SELECT THE MAXIMUM DESIRED
INDOOR HUMIDITY LEVEL (IN PERCENTAGE). THIS VALUE WILL BE USED TO START THE
DEHUMIDISTAT OVERRIDE (AIR EXCHANGE IN HIGH SPEED).
PRESS AND HOLD OK FOR 3 SEC. TO ACCESS THE
SETTINGS MENU. THE BACKLIGHT WILL BE ACTIVATED
DURING ALL THE PROCEDURE.
THE RELATIVE HUMIDITY ARROW AND VALUE WILL FLASH
(DEFAULT SETTING: 45%).
USE UP OR DOWN ARROW TO CHANGE THE
VALUE. THE VALUE CHANGES BY 1% INCREMENTS.
LOWER VALUE: 30%. UPPER VALUE: 55%.
STILL FLASHING.
PRESS OK BUTTON TO ACCEPT THE NEW VALUE AND GO
TO NEXT SETTTING.
TWO LINES ARE FLASHING TO SHOW THAT OFF¹ IS IN
STAND BY (DEFAULT CONFIGURATION SETTING).
OR
RECIRCULATION ARROWS ARE TURNING AND rE FLASHES
TO SHOW THAT RECIRCULATION² IS IN STANDBY.
PRESS OK BUTTON TO ACCEPT
AND QUIT SETTING MENU.
USE UP OR DOWN
ARROW TO CHANGE TO
RECIRCULATION IN
STANDBY.
OR
PRESS OK BUTTON TO ACCEPT AND QUIT SETTING
MENU.
1OFF IN STAND BY: ON 20 MIN/H MODE, THE VENTILATION UNIT IS OFF DURING 40 MINUTES
AND EXCHANGE AIR WITH THE OUTSIDE ON LOW SPEED DURING THE
REMAINING 20 MINUTES OF THE HOUR. THIS IS THE DEFAULT VALUE.
2RECIRCULATION IN STAND BY:ON 20 MIN/H MODE, THE VENTILATION UNIT RECIRCULATES
THE INSIDE AIR FOR 40 MINUTES ON HIGH SPEED AND
EXCHANGE AIR WITH THE OUTSIDE ON LOW SPEED DURING
THE REMAINING 20 MINUTES OF THE HOUR.