7 MAINTENANCE
This section describes replacing the internal battery pack, precautions, checking the UPS status and
checking UPS functions.
WARNING! Risk of electric shock. Can cause equipment damage, injury and death. A battery
can present a risk of electrical shock and high short-circuit current.
The following precautions should be observed when working on batteries:
Remove watches, rings and other metal objects.
Use tools with insulated handles.
Wear rubber gloves and boots.
Do not lay tools or metal parts on top of batteries.
Disconnect charging source prior to connecting or disconnecting battery terminals.
If the battery kit is damaged in any way or shows signs of leakage, contact your Vertiv
representative immediately.
Handle, transport and recycle batteries in accordance with local regulations.
Determine if the battery is inadvertently grounded. If it is inadvertently grounded, remove the
source of the ground. Contact with any part of a grounded battery can result in electrical
shock. The likelihood of such shock will be reduced if grounds are removed during installation
and maintenance (applicable to a UPS and a remote battery supply not having a grounded
supply circuit).
7.1 Replacing the Internal Battery Pack
The GXT4 allows you to replace the internal battery pack safely. Refer to Table 7.1 below for internal
battery pack part numbers for GXT4:
UPS MODEL NUMBER
REPLACEMENT INTERNAL
BATTERY PACK MODEL NUMBER
QUANTITY REQUIRED
GXT4-5000RT230
GXT4-5000RT230E
GXT4-240VBATKIT 2
GXT4-6000RT230
GXT4-6000RT230E
GXT4-240VBATKIT 2
GXT4-10000RT230
GXT4-10000RT230E
GXT4-240RTBKIT 2
Table 7.1 Replacement internal battery pack model number