Technical data Liebert EXL S1
105User Manual 10H52226UM60 - Rev. 1 - 01/2017
Transfer time with inverter
synchronous to Bypass
Inverter to Bypass
(ms)
No Break
Bypass to Inverter
(ms)
≤2
Default transfer delay time (inverter to Bypass)
with inverter not synchronized to Bypass (ms)
20
1) For tolerances see IEC/EN 60146-1 or DIN VDE 0558. The data refers to 25°C ambient temperature
2) Nominal input voltage and input frequency
3) In case of 4 wires split input configuration, the primary input and the Bypass input must have a common
neutral reference
4) Referred to derated load conditions
5) With input voltage at nominal value and voltage distortion THD
V
≤1%
6) Value obtained at 25°C ambient starting from a specified load condition
7) For additional information, contact the technical support
8) Maximum allowable value of prospective short-circuit current at the input terminals of the UPS
Notice
Read and heed the information provided on device labels.
UPS model Liebert EXL S1
Power (kVA) 300 400 500