Select frequency converter operation with a fixed output frequency of 50Hz or 60Hz, bypass
disabled (default is Auto-Select with bypass enabled)
Set the Low Battery Warning alarm time from 2 to 30minutes (default is 2 minutes)
Enable/Disable the Auto-Battery test (default is Enable)
Enable/Disable Auto-Restart after removing Remote shutdown (default is Disable)
Set the wiring mode of Remote shutdown (default is normally open)
Set the Auto-Enable output after remote shutdown (default is Disable)
Set the Auto-Battery test to 8, 12, 16, 20, or 26weeks (default is 8weeks)
Select the number of external battery cabinets connected to the UPS to adjust the remaining
run time calculated by Vertiv software products (default is zero)
Select one of multiple output voltages to match various voltages.
UPS MODEL FACTORY DEFAULT SETTING OUTPUT VOLTAGE OPTION
GXT4-500RT120 - GXT4-3000RT120 120 VAC 110, 115, 120 and 127V
GXT4-3000RT208 208 VAC 208 / 220 / 230 / 240V
Table 6.1 Output voltage option
NOTICE
The output voltage settings cannot be changed while the UPS is On and powering connected
loads.
NOTE: Setting the output voltage of the GXT4-500RT120, GXT4-700RT120, and GXT4-1000RT120
models to 110VAC automatically de-rates both the VA and Watt ratings to 95% of the unit’s rating.
Setting the output voltage of the GXT4-1500RT120 and GXT4-2000RT120 models to 110VAC
automatically de-rates both the VA and Watt ratings to 85% of the unit’s ratings, and programming the
output voltage to 115VAC automatically de-rates both the VA and Watt ratings to 95% of the unit’s
rating.
Setting the output voltage of the GXT4-3000RT120 model to 110VAC automatically de-rates both the
VA and Watt ratings to 90% of the unit’s ratings (refer to Specifications on page53 for the VA and
Watt ratings).
NOTE: This program is compatible with UPS models beginning with ‘GXT4,’ as in ‘GXT4-3000RT230.’ It
is not compatible with earlier versions of the Lieber GXT UPS.
A computer running Microsoft® Windows 2000®, Windows XP®, Windows Vista®, Windows7 or
Windows 8 is required to set up and run the configuration program.
Vertiv | Lieber GXT4 Installer/User Guide
40

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv Liebert GXT4 Series and is the answer not in the manual?

Vertiv Liebert GXT4 Series Specifications

General IconGeneral
BrandVertiv
ModelLiebert GXT4 Series
CategoryUPS
LanguageEnglish

Related product manuals