MODEL NUMBER GXT4-500RT120 GXT4-700RT120 GXT4-1000RT120
RATING 500VA/450W 700VA/630W 1000VA/900W
Storage Temperature, °F (°C) 5ºF to 122ºF (-15ºC to 50ºC)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft. (3000 m) at 77ºF (25ºC) without derating
Storage Elevation 50,000 ft. (15000 m) maximum
Audible Noise
<43dBA max @ 3ft. (1m) front and sides
<46dBA max @ 3ft. (1m) rear
< 50 dBA, at 3ft. (1m) rear
< 45 dBA, at 3ft. (1m) front and sides
Agency
Safety UL 1778, cUL Listed
RFI/EMI FCC Class A
Surge Immunity IEC 62040-2 2nd Ed
Transportation ISTA Procedure 1A
Table 9.1 Specifications for GXT4-500RT120, GXT4-700RT120 and GXT4-1000RT120 (con-
tinued)
MODEL NUMBER GXT4-1500RT120 GXT4-2000RT120 GXT4-3000RT120 GXT4-3000RT208
RATING 1500VA/1350W 2000VA/1800W 3000VA/2700W 3000VA/2700W
Dimensions, D × W × H, in. (mm)
Unit
19.7 x 16.9 x 3.4
(497 × 430 × 85)
23.7 x 16.9 x 3.4
(602 × 430 × 85)
Shipping
25.5 x 23.9 x 10.6
(647 x 607 x 270)
29.4 x 23.4 x 10.6
(747 x 607 x 270)
Weight, lb. (kg)
Unit 54.6 (24.8) 56.1 (25.5) 71.4 (32.4)
Shipping 69.6 (31.6) 70.5 (32) 86 (39)
Input AC
Voltage Range (typical) 120-VAC nominal; variable based on output load
208VAC nominal;
variable
based on output load
90 - 100% loading 102VAC/140VAC 177VAC/280VAC
70 - 90% loading 96VAC/140VAC 168VAC/280VAC
30 - 70% loading 84VAC/140VAC 150VAC/280VAC
0 - 30% loading 60VAC/140VAC 115VAC/280VAC
Table 9.2 Specifications forGXT4-1500RT120 to GXT4-3000RT120 and GXT4-3000RT208
Vertiv | Liebert® GXT4™ Installer/User Guide
54