MODEL NUMBER GXT4-48VBATT GXT4-72VBATT
USED W/UPS MODEL
GXT4-500RT120, GXT4-700RT120,
GXT4-1000RT120, GXT4-1500RT120,
GXT4-2000RT120
GXT4-3000RT120, GXT4-3000RT208
RFI/EMI FCC Class A
Surge Immunity IEC 62040-2 2nd Ed
Transportation ISTA Procedure 1A
Table 9.3 Battery cabinet specifications (continued)
AMBIENT TEMPERATURE, °C(°F)
25-30
(77-86)
30-35
(86-95)
35 - 40
(95-104)
Maximum Output Power Factor Derating @ Maximum
Load
100%-
93%
93%-
86%
86%-79%
Table 9.4 Operating Temperature Parameters
NUMBER OF
EXTERNAL
BATTERY
CABINETS
LOAD
PERCENT
OF
CAPACITY
120 VAC RTMODELS
208VAC
RTMODELS
500VA 700VA 1000VA 1500VA 2000VA 3000VA 3000VA
Internal Battery
10% 131 115 84 117 86 83 79
20% 84 62 40 57 41 40 38
30% 44 39 31 36 25 24 23
40% 40 33 24 25 17 16 16
50% 35 28 17 18 12 12 12
60% 31 23 14 14 9 9 9
70% 27 18 11 11 7 7 7
80% 24 15 9 9 5 6 5
90% 21 13 8 7 4 4 4
100% 17 11 7 6 3 3 3
Table 9.5 Battery run times
9 Specifications
57