NUMBER OF
EXTERNAL
BATTERY
CABINETS
LOAD
PERCENT
OF
CAPACITY
120 VAC RTMODELS
208VAC
RTMODELS
500VA 700VA 1000VA 1500VA 2000VA 3000VA 3000VA
Internal Battery
+ 3 External
Battery Cabinets
10% 1809 1628 1209 977 725 695 657
20% 1211 924 648 511 380 372 356
30% 845 637 451 339 250 247 237
40% 652 489 337 251 186 186 181
50% 535 390 265 199 146 147 144
60% 449 322 218 164 119 120 118
70% 385 272 187 139 100 102 101
80% 335 236 162 118 85 87 85
90% 296 208 142 104 74 76 75
100% 264 185 125 90 62 65 64
Internal Battery
+ 4 External
Battery Cabinets
10% 2065 1926 1574 1284 960 921 871
20% 1576 1249 879 668 501 490 471
30% 1150 859 607 449 330 326 313
40% 886 651 456 330 242 241 236
50% 715 525 358 260 191 193 189
60% 605 434 295 212 157 160 156
70% 518 366 249 181 132 135 133
80% 453 318 215 156 113 116 114
90% 399 278 190 138 98 101 99
100% 356 247 169 120 85 88 86
Table 9.5 Battery run times (continued)
9 Specifications
59