Model Voltage FLA WSA OPD
MCM040
208/230V 2.3 3.2 15
380V 1.4 1.9 15
460V 1.4 1.9 15
575V 1.2 1.6 15
MCM080
208/230V 4.6 5.5 15
380V 2.8 3.3 15
460V 2.8 3.3 15
575V 2.3 2.8 15
MCM160
208/230V 9.2 9.8 15
380V 5.6 6.0 15
460V 5.6 6.0 15
575V 4.7 5.0 15
Large Platform
MCL055
208/230V 5.7 7.1 15
380V 2.8 3.5 15
460V 2.8 3.5 15
575V 2.3 2.9 15
MCL110
208/230V 11.4 12.8 15
380V 5.6 6.3 15
460V 5.6 6.3 15
575V 4.7 5.3 15
MCL165
208/230V 17.1 18.5 20
380V 8.4 9.1 15
460V 8.4 9.1 15
575V 7.0 7.6 15
MCL220
208/230V 22.8 24.2 25
380V 11.2 11.9 15
460V 11.2 11.9 15
575V 9.3 9.9 15
1. FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device.
2. 208V–575V premium models must be connected to Wye three-phase systems.
3. Wye 3-phase systems with solidly grounded neutral. Refer to Wye- vs. Delta-Connected Power Supply on the next page.
Table 4.1 Electrical data, three-phase, 60Hz condenser, premium models (continued)
Rated Voltage - Single-
Phase
120 208/230
Watts/Receiver 150 300 150 300
Amps 1.4 2.8 0.7 1.4
Table 4.2 Electrical data, Liebert Lee-Temp
™
receiver, 60Hz
Vertiv | Liebert® MC™ Installer/User Guide | 41