A - 4
Enclosure A - Electrode Humidier
Liebert PCW - UM - 273895 - 04.10.2018
As a precaution, check, at the frequency recommended further on, for deposits and the blackening of the wall of the cylinder, and replace
the cylinder if necessary.
Warning: always disconnect the appliance before touching the cylinder in the event of leaks, as current may be running through the water.
A.4.4 - Replacement and maintenance of other components
Fill solenoid valve: after having disconnected the cables and the tubing, remove the solenoid valve and check the condition of the inlet
lter; clean if necessary using water and a soft brush.
Supply and drain manifold: check that there are no solid residues in the cylinder attachment, remove any impurities. Check that the gasket
(O- ring) not is damaged or cracked; if necessary, replace it.
Drain pump: disconnect the power supply, remove motor body unscrew the fastening three screws; remove any impurities and rinse.
Supply tank & conductivity meter : check that there are no obstructions or solid particles and that the electrodes for measuring the con-
ductivity are clean, remove any impurities and rinse.
Hose kit: check that the hoses are free and do not contain impurities; remove any impurities and rinse.