B - 2
Enclosure B - Technical data table
Liebert PCW - UM - 273895 - 04.10.2018
* ATTENTION Only universal (type B, B+) RCD protective devices are permitted.
NOTES:
* The cables have to be sized in compliance with local standards and according to the type and characteristics (e.g.Amperes) of in-
stallation.
* The data in the tables do not consider the absorbed current from the condensate pump and for other options not explicitly described.
* The specic power of the user- installed switch, must be lower than 300,000 A
2
x s.
* Prescriptions on the dierential relay required to the user:
* For special places (healthcare facilities, etc...) comply with the local regulations;
* For ordinary places, a low sensitivity is suggested (300mA) coordinated with the value of the ground heater (IEC 364): Ra ≤ 50/
Ia (Art.413.1.4.1, CEI 64- 8);
* In case of frequent over- voltages with mains impulse, it is advisable to install a selective dierential and to evaluate the need
for adopting other devices.
Cooling + Heating + Humidity
Fan + electrical heaters +
electrode or infrared humid-
ier (Electrical Heaters are
available in two stages, data
in brackets refer to the 1st
stage)
PH 025
400 V/3 N/50 Hz
+ earth
29 29 40 A “C” 0.75...35 mm
2
PH 030 29 29 40 A “C” 0.75...35 mm
2
PH 035 29 29 40 A “C” 0.75...35 mm
2
PH 040 29 29 40 A “C” 0.75...35 mm
2
PH 045 29 29 40 A “C” 0.75...35 mm
2
PH 060 45 (32) 45 50 A “C” ( 40 A “C”) 0.75...35 mm
2
PH 070 45 (32) 45 50 A “C” ( 40 A “C”) 0.75...35 mm
2
PH 080 45 (32) 45 50 A “C” ( 40 A “C”) 0.75...35 mm
2
PH 095 60 (49) 60 80 A “C” ( 63 A “C”) 0.75...35 mm
2
PH 100 60 (49) 60 80 A “C” 0.75...35 mm
2
PH 110 60 (49) 60 80 A “C” 0.75...35 mm
2
PH 145 60 (49) 60 80 A “C” 0.75...35 mm
2
PH 170 65 (44) 65 80 A “C” (50 A “C”) 0.75...35 mm
2
PH 046 29 29 40 A “C” 0.75...35 mm
2
PH 066 45 (34) 45 50 A “C” ( 40 A “C”) 0.75...35 mm
2
PH 081 45 (34) 45 50 A “C” ( 40 A “C”) 0.75...35 mm
2
PH 091 45 (34) 45 50 A “C” ( 40 A “C”) 0.75...35 mm
2
PH 111 60 (39) 60 80 A “C” ( 63 A “C”) 0.75...35 mm
2
PH 136 60 (39) 60 80 A “C” ( 63 A “C”) 0.75...35 mm
2
PH 161 60 (39) 60 80 A “C” ( 63 A “C”) 0.75...35 mm
2
PH 201 65 (44) 65 80 A “C” ( 50 A “C”) 0.75...35 mm
2
Cooling + Heating + Humidity
Fan + electrical heaters + ul-
trasonic humidier (Electrical
Heaters are available in two
stages, data in brackets refer
to the 1st stage)
PH 045
400 V/3 N/50 Hz
+ earth
21 21 25 A “C” 0.75...35 mm
2
PH 060 37 (26) 37 40 A “C” (32 A “C”) 0.75...35 mm
2
PH 070 37 (26) 37 40 A “C” (32 A “C”) 0.75...35 mm
2
PH 080 37 (26) 37 40 A “C” (32 A “C”) 0.75...35 mm
2
PH 095 53 (41) 53 63 A “C” (50 A “C”) 0.75...35 mm
2
PH 100 53 (41) 53 63 A “C” (50 A “C”) 0.75...35 mm
2
PH 110 53 (41) 53 63 A “C” (50 A “C”) 0.75...35 mm
2
PH 145 53 (41) 53 63 A “C” (50 A “C”) 0.75...35 mm
2
PH 170 58 (46) 58 63 A “C” (50 A “C”) 0.75...35 mm
2
PH 066 37 (26) 37 40 A “C” (32 A “C”) 0.75...35 mm
2
PH 081 37 (26) 37 40 A “C” (32 A “C”) 0.75...35 mm
2
PH 091 37 (26) 37 40 A “C” (32 A “C”) 0.75...35 mm
2
PH 111 53 (41) 53 63 A “C” (50 A “C”) 0.75...35 mm
2
PH 136 53 (41) 53 63 A “C” (50 A “C”) 0.75...35 mm
2
PH 161 53 (41) 53 63 A “C” (50 A “C”) 0.75...35 mm
2
PH 201 58 (46) 58 63 A “C” (50 A “C”) 0.75...35 mm
2