B - 4
Enclosure B - Technical data table
Liebert PCW - UM - 273895 - 04.10.2018
Conguration Model
EC Fan signal
[VDC]*
(3Ph - 400V - 50Hz)
Power factor
cos φ
OA* nominal power [kW] (*)
Double chilled water circuit
version with Liebert
EC Fan 2.0
Downow
Up
PH 040 7.2 1.8 1.16 0.93
PH 060 6.8 3.12 1.96 0.91
PH 080 7.8 4.36 2.84 0.94
PH 110 7.4 5.85 3.78 0.93
PH 145 9.2 10.02 6.66 0.96
PH 170 8.9 12.44 8.24 0.96
Downow
Down
PH 046 8.3 2.46 1.61 0.95
PH 066 6.3 2.48 1.54 0.90
PH 091 7.1 3.22 2.04 0.92
PH 136 7.6 6.03 3.90 0.93
PH 161 8.2 7.17 4.71 0.95
PH 201 8.3 10.28 6.76 0.95
version with EC
Fan Fix Speed
Downow
Up
PH 040 7.8 2 1.27 0.92
PH 060 7.4 3.5 2.20 0.91
PH 080 8.3 4.86 3.12 0.93
PH 110 8 6.6 4.23 0.93
PH 145 9.6 11.04 7.23 0.95
PH 170 9.5 14.44 9.48 0.95
Downow
Down
PH 046 8.8 2.7 1.74 0.93
PH 066 6.9 2.86 1.74 0.88
PH 091 7.6 3.52 2.20 0.90
PH 136 8.2 6.63 4.23 0.92
PH 161 8.7 7.8 5.01 0.93
PH 201 9 11.92 7.76 0.94
NOTE:
The EC fan settings can be modied acting on the control display (see iCOM manual)
(*) Setting for Nominal Airow at standard conditions: ESP: 20 Pa, Filters class F5