38 5 Specications
Vertiv™ | Liebert® PSI5 120 V Input / 120 V Output & 208 V lnput / 208 V Output Installer/User Guide
5.1 Run Times
NOTE: Liebert® PSl5-1100/2200/3000/5000: When using 2 or more external battery cabinets (EBCs),
the UPS load rating will be decreased by 20%. The % load graph on the LCD automatically adjusts to
reflect this derating.
NOTE: Run times are approximate. They are based on new, fully charged batteries at a temperature of
25°C (77°F) with 100% resistive UPS loading.
Table 5-4 PSI5-800RT120
LOAD
INTERNAL
BATTERY ONLY
NUMBER OF EXTERNAL BATTERY CABINETS
1 2 3 4 5 6
% VA W MINUTES
100 800 720 5.5 27 51 76 104 132 161
90 720 648 6.6 31 58 87 118 150 183
80 640 576 8.0 36 67 101 136 173 210
70 560 504 9.9 42 79 118 160 202 246
60 480 432 12.5 51 96 144 193 244 295
50 400 360 16.2 64 119 178 239 300 363
40 320 288 21.7 84 155 230 306 384 462
30 240 216 30.5 116 213 313 415 517 620
20 160 144 44.4 167 303 441 581 721 862
10 80 72 85.6 313 552 79'2 1034 1276 1519
Table 5-5 PSI5-1100RT120
LOAD
NUMBER OF EXTERNAL
BATTERY CABINETS
LOAD
NUMBER OF EXTERNAL BATTERY
CABINETS
INTERNAL
BATTERY ONLY
1 2 3 4 5 6
% VA W MINUTES % VA W MINUTES
100 1100 990 4.6 20 100 880 792 48 71 95 120 147
90 990 891 5.6 23 90 79'2 713 54 81 109 138 167
80 880 79'2 6.8 27 80 704 634 63 94 126 159 193
70 770 693 8.5 32 70 616 554 75 111 149 188 228
60 660 594 11.0 39 60 528 475 91 134 179 226 273
50 550 495 13.7 48 50 440 396 113 167 222 279 336
40 440 396 18.7 63 40 352 317 147 216 286 357 429
30 330 297 27.0 89 30 264 238 205 298 393 488 584
20 220 198 40.1 131 20 176 158 294 423 553 684 816
10 110 99 87.4 278 10 88 79 545 774 1003 1233 1463