NetSure
™
Control Unit (NCU)
User Manual, UM1M830BNA
Spec. No: 1M830BNA, 1M830DNA Code: UM1M830BNA
Model No: M830B, M830D Revision M, May 12, 2017
Current 1 above High 1 limit.
Check why current is high.
Current 1 above High 2 limit.
Current 5 above High 1 limit.
Current 5 above High 2 limit.
More than one converter has failed.
Check input voltage to converters. Replace
converters.
A converter cannot be detected by the
Controller.
Reset the Converter Lost alarm. Replace
defective converter.
No response from all converters.
Check the connectors and cables or the CAN
loop. Replace the controller.
Over current condition exists.
A converter is in protected mode.
Refer to Converter User Manual for
troubleshooting information.
A converter has lost communications with
the controller.
Check communications cables. Reset the
Communication Fail alarm. Replace the
converter.
A converter has an over temperature
condition.
Check why temperature is high.
A converter has an overvoltage condition.
Refer to Converter User Manual for
troubleshooting information.
A converter’s fan has failed.
A converter is in power limit.
Input voltage to a converter is low.
A converter has a fault condition.
Refer to Converter User Manual for
troubleshooting information.
A converter’s EEPROM has failed.
A converter is in thermal shutdown.
Converter module ID’s overlap.
A converter has an under voltage condition.
(The hysteresis value is 2V.)
A converter has an over voltage condition.
(The hysteresis value is 2V.)
A converter has an under voltage condition.
(The hysteresis value is 1V.)
A converter has an over voltage condition.
(The hysteresis value is 1V.)
Converter alarm summary (one or more
alarms designated as converter is active).