Chapter 1 Product Introduction
7
RDU501 Intelligent Monitoring Unit User Manual
Main functions
Descriptions
3. Provide an alarm test function to test whether the user receives the alarm reminder
information.
4. Can check the balance of the SMS MODEM phone card
Alarm linkage
1. Can be customized according to user requirements
2. DO1 alarm output
3. Can be combined with device signals, parameters and alarms to control the device
4. Interactive with photographing and video recording
5. Have the following logical components
1) AND means
“and”
2) OR means
“or”
3) NOT means
“Not”
4) XOR means
“and/or”
5) GT means “>” 6) LT means “<”
7) DS means
“delay”
System settings
Monitoring unit
Collect RDU501 system information
Network settings
1. IP, subnet mask, gateway, DNS and other related network information settings
2. Authority settings for accessing RDU501 from the upper management platform
3. SNMP settings
4. Security Settings
User management
Add, modify, and delete user information
System Upgrade
Upgrade the app online
Time calibration
Calibrate the RDU501 real-time clock
Restore defaults
Restart RDU501 and restore default configuration
Site information
settings
Modify site information online
Authorization code
management
Extend RDU501 function and access capability through authorization code
Title bar settings
Set the title above the web page
About RDU501
Display product serial number, feature code and version information of RDU501, and
provide download of user manual
1.3 Technical Specifications
1.3.1 Environmental Specifications
The environmental specifications of RDU501 are shown in Table 1-16.
Table 1-16 Environmental conditions
Items
Requirements
Application site
Usually a data center or computer room, usually with an air conditioning environment
Operating
temperature
0˚C to +60˚C
Relative humidity
≤95%RH, no condensation
Use environment
The dust meets the indoor standard of the GR-63 without corrosive gases, flammable gases, oil mist,
water vapor, dripping or salt, etc.
Atmospheric
pressure
70kPa to 106kPa
Storage temperature
20˚C to
70˚C
Cooling method
Convection cooling
Distribution network
TT/TN
Protection level
IP20
1.3.2 Mechanical Specifications
The mechanical specifications of RDU501 are shown in Table 1-17