41
Vertiv I VRC Self-Contained System I User Manual
basis to rule out discrepancies.
VRC1 Series
Date:
Prepared by:
Model:
Serial number:
Type
Maintenance
Components:
Item
Result
Monthly:
Filters
Check for restricted air flow
Check the filter cleanliness
Clean the filter
Evaporator fan
and condenser
fan
Check if fan blades are distorted
Check whether the fan generates noise during operation
Semi-annual
ly:
Compressor
Signs of oil leakage
Check whether the compressor vibrates or makes noise
during operation
Refrigerant
system
Suction pressure
Discharge pressure
Superheat
EEV electric
board
Check whether the wiring and coil of the electronic
expansion valve control board are loose
Check electrical connections
Check the surface for signs of corrosion
7.3.4 Drain Pipe
Inspect the drain pipe for normal operation every 6 months.
Ensure no pipe buckling is present. If the pipe buckling happens, the new pipe should be used.
Ensure that reservoir, pump filter and inlet tube are free of sludge and debris. If not, please clean it.
Figure 7-2 Condensate pump kit
Pump filter
Pump power cable
Pump
Pump communication cable
Pipe 1 (ID=6mm)
Pipe 3 (ID=6mm)
Pipe 2 (ID=6mm)
Reservoir

Table of Contents

Other manuals for Vertiv VRC1 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv VRC1 Series and is the answer not in the manual?

Vertiv VRC1 Series Specifications

General IconGeneral
BrandVertiv
ModelVRC1 Series
CategoryFreezer
LanguageEnglish

Related product manuals