Troubleshooting Party Mode Communications
Ifyoucan’tcommunicatewithaMicroLYNXinpartymode,rstmakesure
that commands are preceded with the correct address and terminated with
[Ctrl-J]. Also remember that the unit will stop listening if you send a wrong
address. Send a [Ctrl-J]andtryagain.Ifitstilldoesn’twork,readon.
If using hardware switch addressing
•Are you sending a lower case address?
The address is uppercaseA-G.Theunitswillnotrespondtolowercase.
•Did you remember to cycle power or [Ctrl-C] after setting the switches?
The address assignment takes place only after power up or [Ctrl-C].
If using software addressing
•Did you enclose the desired address in quotes (DN=“x”)?
While quotes are not required when sending commands to the controller,
during assignment the address must be enclosed within quotes.
•Are the switches all off?
If not, the switch address will override the software address on power
up.Youwillhavetoresetthesoftwareaddressusingtheprocedureon
page 26.
•Did you accidentally set the wrong address?
Youmayhaveinadvertentlysettheaddresstoanunintendedcharacter
orwrongcase.Torecover,settheswitchestoanyunusedaddress(A-G)
and cycle power or send a [Ctrl-C], then reset the software address using
theprocedureonpage26.IfaddressesA-Gareallused,temporarily
remove from system and reset address, then reinstall in system.
If using RS-232
•Is the unit connected to RS-232 set to Host=true (1)?
If not, disconnect all other units and set the Host mode as described in
step 8 on page 26.
•Did you set more than the first MicroLYNX to Host=true?
Only the unit actually connected to the RS-232 cable can be the host; all
othersmusthavethehostsettofalse(0).Disconnectcommunication
cables from all units. Connect the RS-232 cable to each unit in turn and
checktheHostsettingbysendingPRINTHOST.Thereplyshouldbe
FALSEforallbuttherstunitinthesystem.Ifrequired,sendHOST=0to
the clear host flag.