10. Configuration
This section is intended mainly for stand-alone applications
For grid connected Energy Storage Systems (ESS) please see https://www.victronenergy.com/live/ess:start
• Settings may only be changed by a suitable qualified installer with the appropriate training, and subject to local requirements.
Please contact Victron for further information or necessary training.
• Read the instructions thoroughly before implementing changes.
• During setting of the charger, the AC input must be removed.
10.1. Standard settings: ready for use
On delivery, the product is set to standard factory values. In general, these settings are suitable for single-unit operation.
WARNING
Possibly, the standard battery charging voltage is not suitable for your batteries! Refer to the manufacturer's
documentation, or to your battery supplier!
Standard factory settings
Setting Value
Inverter frequency 50 Hz
Input frequency range 45 – 65 Hz
Input voltage range 180 – 265 VAC
Inverter voltage 230 VAC
Stand-alone / parallel / 3-phase stand-alone
AES (Automatic Economy Switch) off
Ground relay on
Charger on / off on
Battery charge curve four-stage adaptive with BatterySafe mode
Charging current 100% of the maximum charging current
Battery type Victron Gel Deep Discharge (also suitable for Victron AGM Deep Discharge)
Automatic equalisation charging off
Absorption voltage 28.8 V / 57.6 V
Absorption time up to 8 hours (depending on bulk time)
Float voltage 27.6 V / 55.2 V
Storage voltage 26.4 V / 52.8 V (not adjustable)
Repeated absorption time 1 hour
Absorption repeat interval 7 days
Bulk protection on
AC input current limit 32A (= adjustable current limit for PowerControl and PowerAssist functions)
UPS feature on
Dynamic current limiter off
WeakAC off
BoostFactor 2
Programmable relay alarm function
PowerAssist on
10.2. Explanation of settings
Settings that are not self-explanatory are described briefly below. For further information, please refer to the help files in the soft-
ware configuration programs.
Inverter frequency
Output frequency if no AC is present at the input.
Adjustability: 50 Hz; 60 Hz
MultiPlus-II GX