Vitodens 200-W B2HA 80 to 100, 285 to 352 Installation
5685 827 - 14
60
Additional Information
Technical Data
*A For high altitude installations 5,000 - 10,000 ft. (1500 m - 3000 m), the input for model B2HA 100, 352 will have an
altitude de-ration of 14% for 5,000 ft. (1500 m) and 29% for 10,000 ft. (3000 m) average of 2.8% / 1,000 ft. (305 m).
*B Tested to AHRI, BTS-2000 Testing Standard Method to Determine Efficiency of Commercial Heating Boilers.
*1 Output based on 140ºF (60ºC), 120ºF (49ºC) system supply/return temperature.
*2 If the gas supply pressure exceeds the maximum gas supply pressure value, a separate gas pressure regulator
must be installed upstream of the heating system.
*3 See “Waterside Flow” on page 30 of this manual.
*4 Net AHRI rating based on piping and pick-up allowance of 1.15.
*5 Output based on 180ºF (82ºC), 80ºF (26ºC) system supply/return temperature.
Boiler Model No. B2HA 80, 285 88, 311 *A 100, 352 *A
CSA input Natural Gas (NG)
CSA input Liquid Propane Gas (LPG)
CSA output NG
CSA output LPG
MBH
(kW)
MBH
(kW)
MBH
(kW)
MBH
(kW)
71-285
(21-83)
104-285
(30-83)
*1 65-260
(19-76)
*1 95-260
(28-76)
71-311
(21-91)
104-311
(30-91)
*5 67-294
(20-86)
*5 98-294
(29-86)
71-352
(21-103)
104-311
(30-91)
*5 67-333
(20-98)
*5 98-333
(29-98)
DOE/AHRI Gross output
Net AHRI Rating *4
MBH
(kW)
MBH
(kW)
--
--
226
(66.2)
292
(85)
254
(74)
329
(96)
286
(84)
Heat exchanger surface area ft.
2
(m
2
)
28.88
(2.68)
28.88
(2.68)
28.88
(2.68)
Min. gas supply pressure
Natural gas
Liquid propane gas
“w.c.
“w.c.
4
10
4
10
4
10
Max. gas supply pressure *2
Natural gas
Liquid propane gas
“w.c.
“w.c.
14
14
14
14
14
14
ANSI Z21,13/CSA 4.9
Thermal efficiency % -- 94.5 94.5
AHRI, BTS-2000 *B
Combustion efficiency
Thermal efficiency
%
%
--
--
94.2
94.0
94.0
93.5
A.F.U.E. % 92.0 -- --
Weight lbs
(kg)
194
(88)
194
(88)
194
(88)
Boiler water content USG
(L)
3.4
(12.8)
3.4
(12.8)
3.4
(12.8)
Boiler max. flow rate *3 GPM
(L/h)
25
(5700)
25
(5700)
25
(5700)
Max. operating pressure
at 210ºF (99ºC)
psig
bar
60
4
60
4
60
4
Boiler water temperature
- Adjustable high limit (AHL) range
space heating (steady state)
DHW production
- Fixed high limit (FHL)
ºF
(ºC)
ºF
(ºC)
ºF (ºC)
68 to 185
(20 to 85)
185
(85)
210 (99)
68 to 185
(20 to 85)
185
(85)
210 (99)
68 to 185
(20 to 85)
185
(85)
210 (99)
Boiler connections
Boiler heating supply and return
Pressure relief valve
Drain valve
Boiler supply/return for
indirect-fired DHW storage tank
(field supplied)
Gas valve connection
NPTM
NPTF
(male
thread)
NPT
NPTF
1b in.
¾ in.
¾ in.
1b in.
1 in.
1b in.
¾ in.
¾ in.
1b in.
1 in.
1b in.
¾ in.
¾ in.
1b in.
1 in.