Power supply
Danger
Incorrectly executed electrical installations can
result in injuries from electrical current and dam-
age to the appliance.
Connect the power supply and implement all
safety measures (e.g. RCD circuit) in accord-
ance with the following regulations:
IEC 60364-4-41
VDE regulations
Connection conditions of the local grid opera-
tor
Install an isolator in the power cable to provide
omnipolar separation from the mains for all active
conductors, corresponding to overvoltage cate-
gory III (3 mm) for complete isolation. The isolator
must be fitted in the permanent electrical installation,
in line with installation requirements.
We also recommend installing a pulse current-sensi-
tive RCD (RCD class A ).
Connect the power cable to the electricity supply
using a fixed connection.
If the power supply to the appliance is connected
with a flexible power cable, ensure that the live con-
ductors are pulled taut before the earth conductor in
the event of strain relief failure. The length of the
earth conductor wire will depend on the design.
Max. fuse rating 16 A.
Danger
The absence of system component earthing can
lead to serious injury from electric current if an
electrical fault occurs.
The appliance and pipework must be connected
to the equipotential bonding of the building.
WiFi operational reliability and system requirements
WiFi router system requirement
WiFi router with activated WiFi:
The WiFi router must be protected by a sufficiently
secure WPA2 password.
The WiFi router must always have the latest firm-
ware update.
Do not use unencrypted connections between the
heat generator and the WiFi router.
Internet connection with high availability:
Flat rate (flat rate tariff without restriction on time or
data volume)
Dynamic IP addressing (DHCP, delivered condition)
in the network (WiFi):
Have this checked on site, and if required set up, by
an IT expert prior to commissioning.
Set routing and security parameters in the IP net-
work (LAN):
Enable port 80, port 123, port 443 and port 8883 for
direct outward connections.
Have this checked and, if necessary, set up on site
by an IT expert before commissioning.
Wireless signal range of WiFi connection
The range of wireless signals may be reduced by
walls, ceilings and interior fixtures. These weaken the
wireless signal, causing poor reception due to the fol-
lowing circumstances.
On their way between transmitter and receiver, wire-
less signals are damped, e.g. by air or when pene-
trating walls.
Wireless signals are reflected by metallic objects
e.g. reinforcements embedded in walls, metal foil of
thermal insulation and thermal glazing with metal-
lised thermal vapour deposit.
Wireless signals are isolated by service ducts and
lift shafts.
Wireless signals are disrupted by devices that also
operate with high frequency signals. Maintain a dis-
tance of at least 2 m from these devices:
Computers
Audio and video systems
Devices with active WiFi connection
Electronic transformers
Pre-ballasts
Install the heat generator as close as possible to the
WiFi router to ensure a good WiFi connection. The sig-
nal strength can be displayed on the heat generator
(see the operating instructions).
Note
The WiFi signal strength can be increased with com-
mercially available WiFi repeaters.
Angle of penetration
The reception quality remains best if radio signals hit
the walls vertically.
Installation sequence
Electrical connections (cont.)
6151778
Installation