EasyManua.ls Logo

Viessmann B2TF - Page 39

Viessmann B2TF
128 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
39
A
B
C
Fig. 29
A
Cover panel
B
Test connector
C
Type plate
Danger
CO formation as a result of incorrect burner
adjustment can have serious health implications.
Carry out a CO test before and after work on
gas appliances.
Operation with LPG
Purge the LPG tank twice on commissioning/replace-
ment. Vent the tank and gas connection line thoroughly
after purging.
01. Close the gas shut-off valve.
02.
Undo clips and remove cover panel
A
.
03.
Undo screw in test connector
B
on the gas train,
but do not remove it. Connect the pressure gauge.
04. Open the gas shut-off valve.
05. Test the static pressure and record it in the report.
Set value: Max. 57.5 mbar (5.75 kPa).
06. Start the boiler.
Note
During commissioning, the appliance can enter a
fault state if there are airlocks in the gas line.
Reset the appliance after approx. 5 s (see operat-
ing instructions).
07. Check the supply (flow) pressure. For set values,
see the following table.
Note
Use a suitable measuring device with a resolution
of at least 0.1 mbar (0.01 kPa) to check the supply
pressure.
08. Record the actual value in the report.
Implement measures as indicated in the table
below.
09. Shut down the boiler. Close the gas shut-off valve.
10. Remove the pressure gauge. Tighten the screw in
test connector
B
.
11. Open the gas shut-off valve and start the appli-
ance.
Danger
Gas escaping from the test connector leads
to a risk of explosion.
Check gas tightness at test connector
B
.
12.
Fit cover panel
A
.
Commissioning, inspection, maintenance
Checking the static pressure and supply pressure
6151778

Table of Contents

Related product manuals