104
Meter reading Fill and top-
up water
Total water
volume
Total hardness pH value Date
Feedwater Boiler water
m
3
m
3
m
3
Settings and test values
Settings and test values Set value Commissioning Maintenance/
service
on
by
Static pressure mbar
kPa
≤ 30
≤ 3.0
Supply pressure (flow pres-
sure)
=
For natural gas E
mbar
kPa
17 - 25
1.7 - 2.5
=
For natural gas L
mbar
kPa
20 - 30
2 - 3
Tick gas type.
Carbon dioxide content CO
2
For natural gas E and L
■
At lower heating output % by vol. 7.2 - 9.2
■
At upper heating output % by vol. 7.7 - 9.2
Oxygen content O
2
■
At lower heating output % by vol. 4.4 - 7.9
■
At upper heating output % by vol. 4.4 - 6.9
Commissioning/service reports
Fill and top-up water
5839829
Appendix