1.
2.
X3
3.
Fig. 33
3. Disconnect plug "X3" from the control unit.
100
10
-20 -10 0 10 20 30
Temperature in °C
6
8
20
40
60
80
200
Resistance in kΩ
Fig. 34 Sensor type: NTC 10 kΩ
4. Measure the resistance of the outside temperature
sensor across terminals "X3.1" and "X3.2" on the
disconnected plug. Compare with the curve.
5. If the results are very different from the curve, dis-
connect the wires from the sensor. Repeat the test
directly on the sensor.
6. Depending on the result, replace the lead or the
outside temperature sensor.
Maintenance
Checking the outside temperature sensor
5839829