EasyManua.ls Logo

Viessmann CIB - Page 37

Viessmann CIB
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
37
Value, ad-
dress 00: ...
Description
2 1 heating circuit without mixer A1 (heating circuit 1), with DHW heating (code is set automatical-
ly)
3 1 heating circuit with mixer M2 (heating circuit 2), without DHW heating
4 1 heating circuit with mixer M2 (heating circuit 2), with DHW heating
5 1 heating circuit without mixer A1 (heating circuit 1) and 1 heating circuit with mixer M2 (heating
circuit 2), without DHW heating (code is set automatically)
6 1 heating circuit without mixer A1 (heating circuit 1) and 1 heating circuit with mixer M2 (heating
circuit 2), with DHW heating (code is set automatically)
7 1 heating circuit with mixer M2 (heating circuit 2) and 1 heating circuit with mixer M3 (heating
circuit 3), without DHW heating
8 1 heating circuit with mixer M2 (heating circuit 2) and 1 heating circuit with mixer M3 (heating
circuit 3), with DHW heating
9 1 heating circuit without mixer A1 (heating circuit 1), 1 heating circuit with mixer M2 (heating cir-
cuit 2) and 1 heating circuit with mixer M3 (heating circuit 3), without DHW heating (code is set
automatically)
10 1 heating circuit without mixer A1 (heating circuit 1), 1 heating circuit with mixer M2 (heating cir-
cuit 2) and 1 heating circuit with mixer M3 (heating circuit 3), with DHW heating (code is set au-
tomatically)
System examples
Coding in the delivered condition Possible change
Code 1
77:1 LON subscriber number, if LON
communication module is installed
77:2
to
77:99
LON subscriber number, adjustable
from 1 to 99:
1 - 4 = Boiler
5 - 9 = Do not adjust
10 - 90 = Vitotronic 200-H
98 = Vitogate
99 = Vitocom
Note
Allocate each number only once.
Detached house/apartment building
7F:1 Detached house 7F:0 Apartment building
Holiday program and time program
for DHW heating can be set sepa-
rately
Lock out controls
8F:0 Operation enabled in standard
menu and extended menu.
Note
The relevant code is only enabled
when you exit the service menu.
8F:1 Operation is blocked in standard
menu and extended menu. Emis-
sions test mode can be activated.
8F:2 Operation is enabled in standard
menu, but blocked in extended
menu. Emissions test mode can be
activated.
Code 1
General/Group "1" (cont.)
5839829
Codes

Table of Contents

Related product manuals