43
Coding in the delivered condition Possible change
Party mode time limit
F2:8 Time limit for party mode or exter-
nal operating program changeover
via pushbutton: 8 h (only for
weather-compensated control
units)
*1
F2:0
No time limit for party mode
*1
F2:1
to
F2:12
Time limit adjustable from 1 to 12 h
*1
Pump control in "Only DHW"
F6:25 In "Only DHW" mode, the heating
circuit pump is constantly on (only
for constant temperature control
units)
F6:0 In "Only DHW" mode, the heating
circuit pump is permanently off.
F6:1
to
F6:24
In "Only DHW" mode, the heating
circuit pump is started 1 to 24 times
per day for 10 min each time.
Pump control in "Standby mode"
F7:25 In "Standby mode", the heating cir-
cuit pump is constantly on (only for
constant temperature control units)
F7:0 In "Standby mode", the heating cir-
cuit pump is constantly off
F7:1
to
F7:24
In "Standby mode", the heating cir-
cuit pump is started 1 to 24 times
per day for 10 min each time.
Start temperature raising
F8:-5 Temperature limit for terminating
reduced mode -5 °C.
Observe setting for coding address
"A3". (only for weather-compensa-
ted control units)
F8:+10
to
F8:-60
Temperature limit adjustable from
+10 to -60 °C
F8:-61 Function disabled
End temperature raising
F9:-14 Temperature limit for raising the re-
duced set room temperature
-14 ºC. (only for weather-compen-
sated control units)
F9:+10
to
F9:-60
Temperature limit for raising the set
room temperature to the value se-
lected for standard mode adjustable
from
+10 to -60 °C
Set flow temperature increase
FA:20 Increasing the set boiler water
temperature or set flow tempera-
ture by 20 % when changing from
operation with reduced room tem-
perature to operation with standard
room temperature (only for weath-
er-compensated control units).
FA:0
to
FA:50
Temperature rise adjustable from 0
to 50 %
Duration set flow temperature increase
FB:60 Duration for increasing the set boil-
er water or flow temperature (see
coding address "FA") 60 min (only
for weather-compensated control
units).
FB:0
to
FB:240
Duration adjustable from 0 to
240 min
*1
In the "Heating and DHW" program, party mode ends automatically when the system changes over to operation at stand-
ard room temperature.
Code 1
Heating circuit 1, heating circuit 2, heating… (cont.)
5839829
Codes

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Viessmann CIB and is the answer not in the manual?

Viessmann CIB Specifications

General IconGeneral
BrandViessmann
ModelCIB
CategoryBoiler
LanguageEnglish

Related product manuals