45
Value, ad-
dress 00: ...
Description
2 1 heating circuit without mixer A1 (heating circuit 1), with DHW heating (code is set automatical-
ly)
3 1 heating circuit with mixer M2 (heating circuit 2), without DHW heating
4 1 heating circuit with mixer M2 (heating circuit 2), with DHW heating
5 1 heating circuit without mixer A1 (heating circuit 1) and 1 heating circuit with mixer M2 (heating
circuit 2), without DHW heating (code is set automatically)
6 1 heating circuit without mixer A1 (heating circuit 1) and 1 heating circuit with mixer M2 (heating
circuit 2), with DHW heating (code is set automatically)
7 1 heating circuit with mixer M2 (heating circuit 2) and 1 heating circuit with mixer M3 (heating
circuit 3), without DHW heating
8 1 heating circuit with mixer M2 (heating circuit 2) and 1 heating circuit with mixer M3 (heating
circuit 3), with DHW heating
9 1 heating circuit without mixer A1 (heating circuit 1), 1 heating circuit with mixer M2 (heating cir-
cuit 2) and 1 heating circuit with mixer M3 (heating circuit 3), without DHW heating (code is set
automatically)
10 1 heating circuit without mixer A1 (heating circuit 1), 1 heating circuit with mixer M2 (heating cir-
cuit 2) and 1 heating circuit with mixer M3 (heating circuit 3), with DHW heating (code is set au-
tomatically)
System examples
Coding in the delivered condition Possible change
11:... No access to the coding addresses
for the parameters of the combus-
tion controller
11:9 Access to the coding addresses for
the parameters of the combustion
controller open
25:0 Do not adjust (only for constant
temperature mode).
2A:0 Never adjust.
2D:0 Never adjust.
32:0 Without AM1 extension 32:1 With AM1 extension (automatic rec-
ognition)
33:1 Function of output A1 at AM1 ex-
tension: Heating circuit pump
33:0 Function of output A1: DHW circula-
tion pump
33:2 Function of output A1: Circulation
pump for cylinder heating
34:0 Function of output A2 at AM1 ex-
tension: DHW circulation pump
34:1 Function of output A2: Heating cir-
cuit pump
34:2 Function of output A2: Circulation
pump for cylinder heating
35:0 Without EA1 extension 35:1 With EA1 extension (automatic rec-
ognition)
36:0
Function of output
aBJ
at EA1 ex-
tension: Fault message
36:1
Function of output
aBJ
: Feed pump
36:2
Function of output
aBJ
: DHW circu-
lation pump
39:2
Function of output
sA
: Circulation
pump for cylinder heating
39:0
Function of output
sA
: DHW circula-
tion pump
39:1
Function of output
sA
: Heating cir-
cuit pump
Code 2
General/Group "1" (cont.)
5839829
Codes