55
Coding in the delivered condition Possible change
24:40 Start temperature for the thermo-
stat function 40 °C.
Start temperature for thermostat
function
≤
stop temperature for
thermostat function:
Thermostat function e.g. for re-
heating. Switching output
sS
is
switched on if the temperature at
sensor
/
undershoots the start
temperature for the thermostat
function.
Start temperature for thermostat
function
>
stop temperature for
thermostat function:
Thermostat function e.g. for utilis-
ing excess heat. Switching output
sS
is switched on if the tempera-
ture at sensor
/
exceeds the start
temperature for the thermostat
function.
24:0
to
24:100
Start temperature for thermostat
function is adjustable from 0 to
100 K.
25:50 Stop temperature for the thermo-
stat function 50 °C.
Start temperature for thermostat
function
≤
stop temperature for
thermostat function:
Thermostat function e.g. for re-
heating. Switching output
sS
is
switched off if the temperature at
sensor
/
exceeds the start tem-
perature for the thermostat func-
tion.
Start temperature for thermostat
function
>
stop temperature for
thermostat function:
Thermostat function e.g. for utilis-
ing excess heat. Switching output
sS
is switched off if the tempera-
ture at sensor
/
undershoots the
start temperature for the thermo-
stat function.
25:0
to
25:100
Start temperature for thermostat
function is adjustable from 0 to
100 K.
26:1 Priority for DHW cylinder 1 – with
cyclical heating
Only when setting code 20:9.
26:0 Priority for DHW cylinder 1 – without
cyclical heating
26:2 Priority for DHW cylinder 2 – without
cyclical heating
26:3 Priority for DHW cylinder 2 – with cy-
clical heating
26:4 Cyclical heating without priority for
either DHW cylinder
Code 2
Solar/Group "4" (cont.)
5839829
Codes