61
Coding in the delivered condition Possible change
FA:20 Increasing the set boiler water
temperature or set flow tempera-
ture by 20 % when changing from
operation with reduced room tem-
perature to operation with standard
room temperature (only for weath-
er-compensated control units)
FA:0
to
FA:50
Temperature increase adjustable
from 0 to 50 %
FB:30 Duration for increasing the set boil-
er water or flow temperature (see
coding address "FA") 60 min (only
for weather-compensated control
units)
FB:0
to
FB:150
Duration adjustable from 0 to
300 min
1 step 2 min
Code 2
Heating circuit 1, heating circuit 2, heating… (cont.)
5839829
Codes