5.2 Heating water buffer cylinder HPM
Buffer cylinder for integration in a wood combustion system with a
maximum rated heating output of 150 kW. Type HPM 2500
and HPM 3000 can be used for a rated heating output of up to
220 kW.
Version:
■ Steel S 235 JRG2, untreated inside, anti-rust coating outside
■ Operating pressure: max. 3.0 bar; test pressure: 4.5 bar
■ Max. temperature: 95 °C
■ Connections: 8 female connections R 1½ or 2, 4 female connections
R ½, 1 sensor pipe 14 x 1.5 mm, 1 female connection top R 1¼, air
vent valve R 1
Flexible foam insulation for HPM
The insulation is made from 100 mm thick flexible PUR foam elements
with a skai jacket.
Fire safety category B3.
Note
On the inside, there are deflector plates at the connections marked 01.
Immersion heaters should not be inserted here.
e
a
b
c
d
03
f
01
01
01
01
01
01
01
01
02
02
02
02
01
02
01
04
o
k
l
m
n
g
h
Part no. buffer cylinder HPM 7424 132 7424 134
Part no. flexible foam insulation to buffer cylinder HPM 7424 138 7424 140
Type 1500 2500
Capacity l 1500 2304
Type of support Support feet Support feet
Weight
Total weight kg 203 281
Weight of heating water buffer cylinder kg 165 236
Weight of insulation kg 38 45
Dimensions
Height when tilted mm 2195 2395
a mm 380 535
b mm 825 975
c mm 1350 1415
d mm 1760 1855
f Height excl. insulation mm 2150 2280
Height incl. insulation mm 2200 2330
g Diameter without insulation mm 1000 1250
h Diameter with insulation mm 1200 1450
Heating water buffer cylinder
(cont.)