Page 22 ACM Telephone System – AMC-M-A A100K 10430 v.1.0
6 PROGRAMMING GUIDE
6.1 Programming Overview
The main steps for programming of a ACM-M-A-V2 system are:
z Perform cold start
z Configure IP address
z Enter license key
z Configure general user settings
z Configure interface to PA
z Configure external communication
A complete programming procedure is described in the System
Maintenance Manual A100K 10338.
Note: If an existing exchange configuration shall be modified, download
the configuration from the exchange. See section 5.2.5. Do NOT
perform cold start!
6.2 Perform Cold Start
A cold start of the AMC-IP board will delete all previous programming,
load the default database and set the default IP-address to 169.254.1.5
with mask 255.255.0.0 on Eth0.
6.2.1 Cold start procedure
z Turn the exchange mains switch ON
(auto-fuse in the rear of the cabinet)
z Hold the cold start button on the AMC-IP board depressed
z Press the reset button located on the power card briefly
z Keep the cold start button pressed at least 1 sec. after reset.
The AMC status LED will blink green when the boot is ready.
6.2.2 Cold start of AMC application only,
keep IP setting
z Press the reset button located on the power card briefly
z After 10 sec., press the cold start button on the AMC-IP board.
z Keep cold start button pressed until AMC running LED is blinking
green.
Figure 18 Cold start
Figure 19 Cold start to load default database
Figure 20 Cold start and keep IP setting
>1 sec
RESET - AP