Labels E 2200 / E 3000ES
22 wc_si000541gb.fm
2.2 Label Meanings
600 —
601 Refer to back of connection box for further
connection details.
602 Stop!
Do not reset (until HTF leak is repaired and
HTF level is restored)
Red “LOW LEVEL FAULT” light on control
panel indicates HTF is below the minimum
operating level.
Follow procedure below to rectify the fault:
1. Shut off burner switch and pump
switch(es).
2. Find and repair the HTF leak.
3. Add HTF to reservoir up to “MIN” level on
HTF sight gauge.
4. Press manual reset button (below).
5. Turn on burner switch.
6. After burner ignites, turn on pump(s) one
at a time.
603 To prevent loss of Heat Transfer Fluid, the fill
valve must remain LOCKED SHUT (closed)
at all times except as directed in the
Operator’s Manual.