Fault modes
The burner controller fault modes are described below.
Lockout The burner will enter the lockout mode after three unsuccessful
attempts to re-light the flame.
During the lockout mode:
The burner will not fire.
The diagnostic light on the burner controller will flash in half-
second intervals.
The burner fault light on the control panel will illuminate.
To clear the lockout fault so a restart can be attempted, press
and release the reset button. Note: After the third attempt to
manually clear the lockout fault, the burner controller will enter
the restricted lockout mode.
Restricted
lockout
The burner will enter the restricted lockout mode after three
unsuccessful attempts to manually reset the lockout fault.
During the restricted lockout mode:
The burner will not fire.
The diagnostic light on the burner controller will flash in half-
second intervals.
The burner fault light on the control panel will illuminate.
To clear the restricted lockout fault so a restart can be
attempted, press and hold (approximately 30–45 seconds) the
reset button until the diagnostic light flashes once. Note: The
burner will return to the lockout mode with each unsuccessful
burner restart, until a successful heating cycle has occurred.