Cable types (typical)From <=> ToCable
2 x 2 x 0.75 mm
2
1 x Ethernet CAT5
Gas Valve Unit <=> Integrated Automation SystemI
4 x 2 x 0.75 mm
2
2 x 2 x 0.75 mm
2
3 x 2 x 0.75 mm
2
Engine <=> Gas Valve UnitI
4 x 2 x 0.75 mm
2
Gas Valve Unit <=> Fuel gas supply systemI
1 x 2 x 0.75 mm
2
Gas Valve Unit <=> Gas detection systemI
2 x 4 mm
2
(power supply) *
2 x 4 mm
2
(power supply) *
3 x 2 x 0.75 mm
2
Power unit <=> Gas Valve UnitI
3 x 2 x 0.75 mm
2
2 x 5 x 0.75 mm
2
Gas Valve Unit <=> Exhaust gas fan and pre-lube starterI
4 x 2 x 0.75 mm
2
3 x 2.5 x 2.5 mm
2
Exhaust gas fan and pre-lube starter <=> Exhaust gas
ventilation unit
I
NOTE
Cable types and grouping of signals in different cables will differ depending on
installation.
* Dimension of the power supply cables depends on the cable length.
Power supply requirements are specified in section Power unit.
DBAE248994 14-5
14. Automation SystemWärtsilä 31DF Product Guide