PM Integrated Controller 51 Chapter 5 Operations Page
Operations Page
Display
Parameter name
Description
Range Default
Parameter
Appears in
Menu When
Modbus Rela-
tive Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
No Dis-
play
Special Output Func-
tion (1)
Output Error
View reported cause
for output malfunc-
tion.
None (61)
Open (65)
Shorted (127)
Measurement error
(140)
Bad calibration data
(139)
Ambient error (9)
RTD error (14)
Fail (32)
Math error (1423)
Not sourced (246)
Stale (1617)
Can't process (1659)
- - - - - - - - Instance 1
Map 1 Map 2
- - - - 3860
0x87 (135)
1
0xC (12)
- - - - uint
R
[P;Sta]
[oPEr]
Profile Status Menu
Profile Menu appears if:
(PM _ [R, B*, N, E*] _ _ _-_ _ _ _ _ _ _)
* Available with PM8/9 only
* Some parameters in the Profile Status Menu can be changed for the cur-
rently running profile, but should only be changed by knowledgeable
personnel and with caution. Changing parameters via the Profile Status
Menu will not change the stored profile but will have an immediate im-
pact on the profile that is running.
Changes made to profile parameters in the Profiling Pages will be saved
and will also have an immediate impact on the running profile.
[P;Str]
[P.Str]
Profile Status
Profile Start
Select step to act
upon.
1 to 40 1 Always Instance 1
Map 1 Map 2
2520 4340
0x7A (122)
1
1
204 uint
RW
[P;ACr]
[PACr]
Profile Status
Action Request
[nonE] None (61)
[step] Step Start
(89)
[`End] Terminate
(148)
[rESU] Resume (147)
[PAUS] Pause (146)
[ProF] Profile (77)
None Always Instance 1
Map 1 Map 2
2540 4360
0x7A (122)
1
0xB (11)
205 uint
RW
[`StP]
[ StP]
Profile Status
Active Step
View the currently
running step.
1 to 40 0 (none) a profile is
active.
Instance 1
Map 1 Map 2
2526 4346
0x7A (122)
1
4
- - - - uint
R
[S;typ]
[S.typ]
Profile Status
Active Step Type
View the currently
running step type.
UStP] Unused Step
(50)
[`End] End (27)
[``JL] Jump Loop
(116)
[CloC] Wait For Time
(1543)
[W;bo] Wait For Both
(210)
[W;Pr] Wait For Pro-
cess (209)
[`W;E] Wait For
Event (144)
[SoAH] Soak (87)
[``ti] Time (143)
[rAtE] Rate (81)
a profile is
active.
Instance 1
Map 1 Map 2
2544 4364
0x7A (122)
1
0xD (13)
- - - - uint
R
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E: EE-
PROM