Watlow EZ-ZONE
®
PM Integrated Controller 52 Chapter 5 Operations Page
Operations Page
Display
Parameter name
Description
Range Default
Parameter
Appears in
Menu When
Modbus Rela-
tive Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[t;SP1]
[tg.SP]
Profile Status
*Target Set Point
Loop 1
View or change the
target set point of the
current step.
-1,999.000 to
9,999.000°Forunits
-1,128.000 to
5,537.000°C
0.0°F
or
units
-18.0°C
a profile is
active.
Instance 1
Map 1 Map 2
2542 4362
0x7A (122)
1
0xC (12)
- - - - float
RW
[t;SP2]
[tg.SP]
Profile Status
*Target Set Point
Loop 2
View or change the
target set point of the
current step.
-1,999.000 to
9,999.000°Forunits
-1,128.000 to
5,537.000°C
0.0°F
or
units
-18.0°C
a profile is
active.
Instance 1
Map 1 Map 2
- - - - 4434
0x7A (122)
1
0x30 (48)
- - - - float
RW
[aC;sp]
[AC.SP]
Profile Status
Produced Set Point
1
Display the current
set point, even if the
profile is ramping.
-1,999.000 to
9,999.000°Forunits
-1,128.000 to
5,537.000°C
0.0°F
or
units
-18.0°C
Always Instance 1
Map 1 Map 2
- - - - - - - -
- - - - - - - - float
R
[aC;sp]
[AC.SP]
Profile Status
Produced Set Point
2
Display the current
set point, even if the
profile is ramping.
-1,999.000 to
9,999.000°Forunits
-1,128.000 to
5,537.000°C
0.0°F
or
units
-18.0°C
Always Instance 1
Map 1 Map 2
- - - - - - - -
- - - - - - - - float
R
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with
other interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E: EE-
PROM
S: User
Set