Watlow EZ-ZONE
®
PM Integrated Controller • 58 • Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[`r;Lo]
[ r.Lo]
Analog Input (1 to 2)
Range Low
Set the low range for
this function block's
output.
-1,999.000 to 9,999.000 0.0 Sensor Type
is set to
Millivolts,
Volts, Mil-
liamps or
Potentiom-
eter1kΩ.
Instance 1
Map 1 Map 2
392 392
Instance 2
Map 1 Map 2
472 482
0x68 (104)
1 to 2
0x11 (17)
8 float
RWES
[`r;hi]
[ r.hi]
Analog Input (1 to 2)
Range High
Set the high range
for this function
block's output.
-1,999.000 to 9,999.000 9,999 Sensor Type
is set to
Millivolts,
Volts, Mil-
liamps or
Potentiom-
eter1kΩ.
Instance 1
Map 1 Map 2
394 394
Instance 2
Map 1 Map 2
474 484
0x68 (104)
1 to 2
0x12 (18)
9 float
RWES
[`P;EE]
[ P.EE]
Analog Input (1 to 2)
Process Error En-
able
Turn the Process Er-
ror Low feature on
or off.
[`off] Off (62)
[Low] Low (53)
Off Sensor Type
is set to
Millivolts,
Volts, Mil-
liamps or
Potentiom-
eter1kΩ.
Instance 1
Map 1 Map 2
418 388
Instance 2
Map 1 Map 2
498 508
0x68 (104)
1 to 2
0x1E (30)
10 uint
RWES
[`P;EL]
[ P.EL]
Analog Input (1 to 2)
Process Error Low
If the process value
drops below this
value, it will trigger
an input error.
-100.0 to 1,000.0 0.0 Sensor Type
is set to
Millivolts,
Volts, Mil-
liamps or
Potentiom-
eter1kΩ,
and Error
Enable is
set to Low.
Instance 1
Map 1 Map 2
420 420
Instance 2
Map 1 Map 2
500 510
0x68 (104)
1 to 2
0x1F (31)
11 float
RWES
[``t;C]
[ t.C]
Analog Input (1 to 2)
Thermistor Curve
Select a curve to ap-
ply to the thermistor
input.
[```A] Curve A (1451)
[```b] Curve B (1452)
[```C] Curve C (1453)
[CUSt] Custom (180)
Curve A Sensor Type
is set to
Thermis-
tor.
Instance 1
Map 1 Map 2
434 434
Instance 2
Map 1 Map 2
514 524
0x68 (104)
1 to 2
20x6 (38)
- - - - uint
RWES
[``r;r]
[ r.r]
Analog Input (1 to 2)
Resistance Range
Set the maximum
resistance of the
thermistor input.
[```5] 5K (1448)
[``10] 10K (1360)
[``20] 20K (1361)
[``40] 40K (1449)
40K Sensor Type
is set to
Thermis-
tor.
Instance 1
Map 1 Map 2
432 432
Instance 2
Map 1 Map 2
512 522
0x68 (104)
1 to 2
0x25 (37)
- - - - uint
RWES
[`FiL]
[ FiL]
Analog Input (1 to 2)
Filter
Filtering smooths out
the process signal to
both the display and
the input. Increase
the time to increase
filtering.
0.0 to 60.0 seconds 0.5 Always Instance 1
Map 1 Map 2
386 386
Instance 2
Map 1 Map 2
466 476
0x68 (104)
1 to 2
0xE (14)
12 float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other
interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set