Watlow EZ-ZONE
®
PM Integrated Controller 86 Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter name
Description
Range Default
Parameter
Appears
in Menu
When
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Data
Type
&
Read/
Write
[Mb;E]
[Mb.E]
Communications (2)
Modbus TCP En-
able
Activate Modbus
TCP.
[`YES} Yes (106)
[``no] No (59)
Yes Always if
digit 8 is a
"3".
- - - - - - - - - - - - - - - -
[EiP;E]
[EiP.E]
Communications (2)
EtherNet/IP™ En-
able
Activate Ethernet/
IP™.
[`YES} Yes (106)
[``no] No (59)
Yes Always if
digit 8 is a
"3".
- - - - - - - - - - - - - - - -
[ao;nb]
[Ao.nb]
Communications (2)
Implicit Output As-
sembly Size
1 to 20 20 Always if
digit 8 is a
"3" or "5".
- - - - - - - - - - - - - - - -
[ai;nb]
[Ai.nb]
Communications (2)
Implicit Input As-
sembly Size
1 to 20 20 Always if
digit 8 is a
"3" or "5".
- - - - - - - - - - - - - - - -
[`C_F]
[ C_F]
Communications (2)
Display Units
Select which scale to
use for temperature
passed over commu-
nications port 2.
[```F]°F(30)
[```C]°C(15)
°F Always Instance 1
Map 1 Map 2
2490 2970
0x96 (150)
1
6
199 uint
RWE
[Map]
[ Map]
Communications (2)
Data Map
If set to 1 the control
will use PM legacy
mapping. If set to
2 the control will
use new mapping to
accommodate new
functions.
1 to 2 1 if 9
th
digit
of part
number
is a D or
1 other-
wise, 2.
Always - - - - - - - - - - - - - - - -
[`nU;S]
[ nU.S]
Communications (2)
Non-volatile Save
If set to Yes all val-
ues written to the
control will be saved
in EEPROM.
[`yes] Yes (106)
[``no] No (59)
Yes Always if
digit 8 of
the part
number is
2, 3 or 5.
Instance 1
Map 1 Map 2
- -
Instance 2
Map 1 Map 2
- -
96 (150)
2
8
198 uint
RWE
[rtC]*
[`SEt]
Real Time Clock Menu
[hoUr]
[hoUr]
Real Time Clock
Hours
0 to 23 0 Always if
4th digit
in part
number is
a "B" or
"E".
Instance 1
Map 1 Map 2
- - - - 4004
88 (136)
1
3
- - - - uint
RW
[Min]
[Min]
Real Time Clock
Minutes
0 to 59 0 Always if
4th digit
in part
number is
a "B" or
"E".
Instance 1
Map 1 Map 2
- - - - 4006
88 (136)
1
4
- - - - uint
RW
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read with other
interfaces.
* Available with PM4, PM8 and PM9 models only
R: Read
W: Write
E:
EE-
PROM
S:
User
Set

Table of Contents