EasyManua.ls Logo

Watlow Ez-Zone PM8 - Quencharc Wiring Example

Default Icon
101 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Óç
Warning:
Use National Electric (NEC)
or other country-specific
standard wiring and safety
practices when wiring and
connecting this controller to
a power source and to elec-
trical sensors or peripheral
devices. Failure to do so may
result in damage to equip-
ment and property, and/or
injury or loss of life.
Note:
Maximum wire size termina-
tion and torque rating:
0.0507 to 3.30 mm
2
(30 to
12 AWG) single-wire termi-
nation or two 1.31 mm
2
(16
AWG)
0.8 Nm (7.0 lb.-in.) torque
Note:
Adjacent terminals may be
labeled differently, depend-
ing on the model number.
Note:
To prevent damage to the
controller, do not connect
wires to unused terminals.
Note:
Maintain electrical isolation
between analog input 1, digi-
tal input-outputs, switched
dc/open collector outputs and
process outputs to prevent
ground loops.
Note:
The control output common
terminal and the digital com-
mon terminal are referenced
to different voltages and
must remain isolated.
Watlow EZ-ZONE
®
PM PID Controller 20 Chapter 2 Install and Wire
Quencharc Wiring Example
In this example the Quencharc circuit (Watlow
part# 0804-0147-0000) is used to protect PM
internal circuitry from the counter electro-
magnetic force from the inductive user load
when de-engergized. It is recommended that
this or an equivalent Quencharc be used when
connecting inductive loads to PM outputs.
Quencharc
User Load
L
_
K
_
N

Table of Contents