EasyManuals Logo

WEG CFW501 V1.8X User Manual

WEG CFW501 V1.8X
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #150 background imageLoading...
Page #150 background image
Parâmetros de Leitura
15-2 | CFW501
15
P0005 – Output Frequency (Motor)
Adjustable
Range:
0.0 to 500.0 Hz Factory
Setting:
Properties: ro
Access groups
via HMI:
READ
Description:
Real frequency instantly applied to the motor in Hertz (Hz).
P0006 – Inverter Status
Adjustable
Range:
According to Table 15.1: Inverter status - P0006 on page 15-2 Factory
Setting:
Properties: ro
Access groups
via HMI:
READ
Description:
It indicates one of the ten possible inverter status. In Table 15.1: Inverter status - P0006 on page 15-2, a
description of each status is presented, as well as the indication on the HMI.
Table 15.1: Inverter status - P0006
P0006 Status HMI Description
0 Ready Indicates the inverter is ready to be enabled.
1 Run Indicates the inverter is enabled.
2 Sub
Indicates the voltage in the inverter is too low for
operation (undervoltage), and will not accept the
enabling command.
3
Fault
Fxxxx
Indicates the inverter is in the fault status.
4
Self-Tuning
(conf RUN)
Indicates the inverter is executing the Self-Tuning
routine.
5
Configuration
(conf)
Indicates the inverter has incompatible parameter
programming. Refer to section 5.7 SITUATIONS FOR
CONFIG STATUS on page 5-12.
6
DC Braking
(RUN)
Indicates the inverter is applying DC braking to stop
the motor.
7...9 Reserved
-
-