Parâmetros de Leitura
15-2 | CFW501
15
P0005 – Output Frequency (Motor)
Adjustable
Range:
0.0 to 500.0 Hz Factory
Setting:
Properties: ro
Access groups
via HMI:
READ
Description:
Real frequency instantly applied to the motor in Hertz (Hz).
P0006 – Inverter Status
Adjustable
Range:
According to Table 15.1: Inverter status - P0006 on page 15-2 Factory
Setting:
Properties: ro
Access groups
via HMI:
READ
Description:
It indicates one of the ten possible inverter status. In Table 15.1: Inverter status - P0006 on page 15-2, a
description of each status is presented, as well as the indication on the HMI.
Table 15.1: Inverter status - P0006
P0006 Status HMI Description
0 Ready Indicates the inverter is ready to be enabled.
1 Run Indicates the inverter is enabled.
2 Sub
Indicates the voltage in the inverter is too low for
operation (undervoltage), and will not accept the
enabling command.
3
Fault
Fxxxx
Indicates the inverter is in the fault status.
4
Self-Tuning
(conf RUN)
Indicates the inverter is executing the Self-Tuning
routine.
5
Configuration
(conf)
Indicates the inverter has incompatible parameter
programming. Refer to section 5.7 SITUATIONS FOR
CONFIG STATUS on page 5-12.
6
DC Braking
(RUN)
Indicates the inverter is applying DC braking to stop
the motor.
7...9 Reserved
-
-