11.3.3 Error type C
Error type C (Fig. 49):
If type C errors occur, proceed as follows to acknowledge (Fig. 50):
• To change to the menu mode, press the red button.
Menu number <6.0.0.0> flashes on the display.
• Press the red button again.
Menu number <6.0.0.0> appears steady on the display.
On the value display, “- - -” appears.
On the units display, the current incidence (x) as well as the maximum
incidence of the error (y) are displayed in the format “x/y”.
After 300 seconds, the current incidence will be counted up by one.
NOTE:
The error will be acknowledged automatically if the cause of the error
is eliminated.
• Wait until the remaining time is up.
If the current incidence (x) is the same as the maximum incidence of
the error (y), this error can be acknowledged manually.
• Press the red button again.
The error is acknowledged, and the status page is displayed.
Fig. 49: Error type C, flowchart
1
4
8
7
3
6
5
2
Program
step/query
Contents
1 • Error code is displayed
• Motor Off
• Red LED On
2 Error criterion fulfilled?
3 > 5 minutes?
4 • Error counter is incremented
5 Error counter > 5?
6 • SSM is activated
7 Error acknowledged?
8 End; auto control resumes
Yes
No
Fig. 50: Acknowledging error type C
6.0.0.0
6.0.0.0
6.0.0.0
6.0.0.0
S
S
S
3/6
5/6
6/6
---
300
0
12.3
12.3
12.3
E000