Installation and operating instructions Wilo-VeroLine-IP-E, VeroTwin-DP-E 107
11.3.3 Error type C
Error type C (Fig. 49):
If type C errors occur, proceed as follows to acknowledge (Fig. 50):
To change to the menu mode, press the red button.
Menu number <6.0.0.0> flashes on the display.
Press the red button again.
Menu number <6.0.0.0> appears steady on the display.
On the value display, “- - -” appears.
On the units display, the current incidence (x) as well as the maximum
incidence of the error (y) are displayed in the format “x/y”.
After 300 seconds, the current incidence will be counted up by one.
NOTE:
The error will be acknowledged automatically if the cause of the error
is eliminated.
Wait until the remaining time is up.
If the current incidence (x) is the same as the maximum incidence of
the error (y), this error can be acknowledged manually.
Press the red button again.
The error is acknowledged, and the status page is displayed.
Fig. 49: Error type C, flowchart
1
4
8
7
3
6
5
2
Program
step/query
Contents
1 Error code is displayed
Motor Off
Red LED On
2 Error criterion fulfilled?
3 > 5 minutes?
4 Error counter is incremented
5 Error counter > 5?
6 SSM is activated
7 Error acknowledged?
8 End; auto control resumes
Yes
No
Fig. 50: Acknowledging error type C
6.0.0.0
6.0.0.0
6.0.0.0
6.0.0.0
S
S
S
3/6
5/6
6/6
---
300
0
12.3
12.3
12.3
E000
E000
E000