EasyManua.ls Logo

Winterwarm XR - Further Troubleshooting

Winterwarm XR
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
21
INSTRUCTION MANUAL AIR HEATER TYPE XR
The heat exchange sensor consists of two internal
sensors. The readings of these sensors may dier
too much:
Measure the resistance of each sensor. The
resistance should be 20 KΩ at 25 °C and 25
KΩ at 20 °C.
If the measured values dier too much,
replace the sensor.
Case 5: Too many flame failures while burning.
The gas supply is not constant. This results in a
drop in gas supply pressure while burning and
causes the flame to extinguish.
Check the gas supply pressure while the
heater is burning.
The burner pressure for Low fire is too low. This
causes the flame to extinguish because it is too
small to be detected.
Check the burner pressure at Low fire and
adjust if necessary (see §8.1).
Recirculation of flue gas. Due to a problem with the
flue terminal the flue gas is sucked back into the air
inlet. This results into a lack of oxygen and causes
the flame to stop.
Check the flue system and fresh air supply.
Only certified, original parts should be used.
Case 6: Burner fan does not work.
Check if the burner fan is blocked.
Check if the wiring is damaged.
The burner fan is defective.
Case 7: Burner fan rotates at the wrong speed.
Check if the burner fan runs smoothly.
Check if the wiring is damaged.
Case 9: Too many reset actions in a short timespan.
This error will disappear after some time or if the
main power is disconnected for a while.
Case 11: Insucient air passage through the heat
exchanger. Pressure switch does not close.
Check if the combustion fan is running.
Check if the flue system is blocked or restricted.
Check the pressure switch and the connections.
Check the heat exchanger for flue leakage.
Case 12: E-error for more than 24 hours.
Switch the air heater o and on and check the error
code.
Case 13: Internal error.
Isolate the electrical supply and reenergise. If this
does not help:
Replace the burner control unit.
Case 14: Pressure switch is closed in stand-by mode.
Check if the contact is stuck. If so:
Replace the pressure switch.
Check if there is water in the hose. If so:
Dry the hose.
Case 15: Flame detected after closing the gas valve.
Check if the gas valve closes too slow. If so:
Replace the gas valve.
Check if the ionisation electrode is wet. If so:
Dry, clean or replace the electrode.
Case 16: Flame detected before opening the gas valve.
Check if there really is a flame before ignition. If so:
Replace the gas valve.
Check if the ionisation electrode is wet. If so:
Dry, clean or replace the electrode.
Case 19: Heater configuration error
The heater does not know which program to run,
due to a mismatch between the burner control unit
and the display. If so:
Contact your supplier.
9.5 Further troubleshooting
When the air heater does start but shows a dierent
problem than described above, check if the following
problems apply.
9.5.1 Explosive ignition and/or frequent flame failures
Check if the gas control settings are correct (see
§8.1). A correct CO
2
value is important for a proper
ignition.
Check the ignition cable. It should have a
resistance of 1 kΩ.
Check the position of the ignition electrode.
The spark has to be formed between the two
electrodes, not between the electrode and the
burner.

Related product manuals