3.3 Driving the doors with the eleva-
tor controller
- Connect the signals from the elevator control-
ler to connector X1 and X2 of the door opera-
tor.
- Refer to the project delivery documents for the
wiring diagram between the elevator controller
and door operator (see also connection diagram
in chapter 9 -> MIDI or chapter 10 -> SUPRA).
- Check if Test Button operation switch is OFF
S1/1.
- If the door is not at the reference switch (near
by close end) in power up and CLOSE is active
(connected with COMMON) it will move at low
speed as long as the reference (close end) posi-
tion is found.
- After finding the reference switch the door
drive will start with the next OPEN command in
direction open with normal speed drive until
the mechanical end is found.
- Then the door will drive with normal speed in
both directions.
- Check that the safety devices (open button,
photo cells and close force limiter) reopen the
door (see DIP-switch description).
- According to the DIP Switch adjustment (S1/2)
the door is reopend by the elevator control or
automatic by the door.
3.4 Driving the doors by the service
drive buttons
- The Test Buttons only work when the Test but-
ton operation switch (S1/1) is active.
- Check that the door is moving open and close
when the test buttons are pressed.
- In this mode of operation the re-opening of the
door by a safety device is not activated. (ena-
bles the adjustment of the closing force).