This opens an Edit TecJet Configuration screen, (e.g., Figure 5-8), to permit driver configuration setting
changes. The configuration settings are provided in a common area of the Edit TecJet Configuration
screen and on several tabbed screens.
Configuration changes will not take effect until they are loaded to the
control. Review ALL settings shown on ALL tabbed Edit TecJet
Configuration screens to verify all configuration settings are correct
before loading the settings to the control.
An improperly calibrated control could cause an overspeed or other
damage to the engine.
Edit TecJet Configuration - General
This is an edit screen for general control configuration settings. To change a value, highlight the value
and type the desired value. The status bar displays the valid adjustable range for the highlighted value.
Note, Demand Source options may change depending on firmware loaded.
Figure 5-8. Edit TecJet Configuration - General
Fuel Gas Temperature Warning Thresholds - Low Temperature
Sets the temperature, in ºC, which triggers a Fuel Gas Temperature Low warning indication.
Adjustable range: -40 to 25º C
Fuel Gas Temperature Warning Thresholds - High Temperature
Sets the temperature, in ºC, which triggers a Fuel Gas Temperature High warning indication.
Adjustable range: 25 to 90º C
Fuel Gas Pressure Warning Thresholds - Low Pressure
Sets the pressure, in millibar, which triggers a Fuel Gas Pressure Low warning indication.
Adjustable range: 0 to 1600 mbar
Fuel Gas Pressure Warning Thresholds - High Pressure
Sets the pressure, in millibar, which triggers a Fuel Gas Pressure High warning indication.
Adjustable range: 0 to 1600 mbar