EasyManua.ls Logo

Worcester Greenstar 25Si Compact - Service and Spares (Continued); 7.6 Flue Gas Analysis

Worcester Greenstar 25Si Compact
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SERVICE AND SPARES
Greenstar Si Compact
ErP
- 6 720 813 278 (2015/07) 43
Re-check the fan pressure readings.
If the boiler, after completing the above checks, fails the fan pressure
test then contact Worcester, Bosch Group for advice.
After the measurements are taken switch the boiler off.
Remove the combustion air intake pipe.
Disconnect the manometer and replace the test point cover.
Replace the combustion air intake pipe.
7.6 FLUE GAS ANALYSIS
Combustion test
Connect the flue gas analyser to the flue gas sampling point (1) as
shown in the figure below.
Ensure that the probe reaches the centre of the flue gas exhaust,
adjust the cone on the probe so that it seals the sample point and
correctly positions the end of the probe.
Press the and buttons together
The chimney sweep symbol will be displayed at the top of the
screen.
“Max” will flash at the bottom of the screen.
The boiler will ramp up to maximum output in approximately 30 to
35 seconds.
Run the boiler at maximum output for at least 10 minutes.
▶Check the CO/CO
2
readings against the information in table 26.
Fig. 69 Combustion test
Set the boiler to minimum power by pressing the down arrow button.
“Min” will flash at the bottom left of the screen.
The boiler will take 30 to 35 seconds to ramp down to minimum
output.
Allow the boiler to stabilise at minimum output.
▶Check the CO/CO
2
readings against those in tables 26 and 27
Return the boiler to maximum, by pressing the UP arrow button, and
re-check the CO/CO
2
.
“Max” will flash at the bottom left of the screen.
The boiler will take approximately 30 to 35 seconds to ramp up to
maximum output.
Allow the boiler to stabilise at maximum output.
If correct, press the button and the boiler will return to normal
operation.
Re-assemble and refit boiler case.
Example of a Natural Gas appliance reading:
•Maximum CO
2
reading taken = 9.5%
The minimum CO
2
reading must be between 8.0% and 9.3%
(a minimum 0.2 lower than the maximum reading of 9.5%)
If the CO
2
is out of tolerance then please check:
the gas inlet pressure,
▶the gas rate,
the fan test pressure,
the condition of burner,
the flue and air intake, plus any possible blockages in the condensate
disposal.
for leaks or obstructions in the gas way,
that the injector is clean.
After all checks have been and the CO
2
is still out of tolerance then the
gas valve must be replaced.
NOTICE: Combustion testing
Combustion testing must be carried out by a
competent person. Testing must not be attempted
unless the person carrying out the combustion check
is equipped with a calibrated Combustion Analyser
conforming to BS 7927 and is competent in its use.
NOTICE: Gas inlet pressure
Ensure that the gas inlet pressure has been checked
and is satisfactory, refer to section 6.5.1
When running in maximum output, and the water
temperature is 65°C or less, the boiler will operate both
the central heating and DHW circuits with the diverter
valve in the mid position. It will be necessary to run
sufficient water through the DHW circuit to ensure that
the boiler will not cycle on low heating demands.
This is to allow sufficient time for the setting procedure.
When the water temperature reaches 75°C the diverter
valve will switch to CH only.
eco
6720646608-105.1Wo
1
NOTICE: Minimum CO
2
The minimum CO
2
reading must be at least 0.2 lower
that the maximum CO
2
reading.
NG Appliances
Output CO
2
Reading CO Reading
Maximum setting
(measured after
10 minutes
Between 8.5 and 10.1. Less than 200ppm
Minimum setting
(measured after
10 minutes
A minimum 0.2 lower than the
maximum reading taken but
above 7.5%
Less than 50ppm
Table 26 NG CO/CO
2
settings
LPG Appliances
Output CO
2
Reading CO Reading
Maximum setting
(measured after
10 minutes
Between 9.8 and 11.1. Less than 200ppm
Minimum setting
(measured after
10 minutes
A minimum 0.2 lower than the
maximum reading taken but
above 8.5%
Less than 50ppm
Table 27 LPG CO/CO
2
settings

Table of Contents

Related product manuals