Operating During Transition Between Grid Mode and Battery Mode
975-0799-01-01 71
Settings
Setting Name
Setting
Number
Default
Value
Range of
Values
Description
Inverter Ignition Control
01 OFF
OFF
LOT
ATO
See Description of Ignition Control Features on page 40.
LBCO Voltage
02 10.5 10.0 to 12.8
The voltage setting value can be adjusted by 0.1 increments. The
inverter is able to recover automatically at LBCO voltage +
0.2volts.
LBCO Shutdown Delay
Timer
03 300 1 to 300
When the range is from 1 to 20, the timer setting value can be
adjusted by 1-second increments. When the range is from 20 to
300, the timer setting value can be adjusted by 10-second
increments.
LBCO Recovery Voltage
04 13.1
10.2 to 16.0
and OFF
The range is from LBCO voltage + 0.2 to 16, adjusted by 0.1
increments. Selecting OFF or a higher value than the battery’s
actual fully-charged voltage level will disable the auto-recovery
feature. You may manually reset the inverter/charger when the low
battery cut off event occurs.
Power Save Time
05 25 OFF, 1 to 25
The range is from 1 to 25, adjusted by 1-hour increments. The next
setting after 25 is OFF.
Power Save (Load
Sensing) Mode
06 dIs
ENA (enable),
DIS (disable)
When enabled, the inverter/charger’s “no load” loss can be
reduced further when total load is less than 25watts.