169
Q9: The service life of tank chain?
The bending resistance is 5 million times and the bending radius is 50 mm.
Q10: How to connect bus control BD board and JA-NE-L?
A-A1, B-B1, SG-SG when one axis running; the PLC BD board and the terminal resistor of the last JA-NE-L
board of electrical connection should be ON when multi-axis running; and the terminal resistance of JA-NE-L
board in the middle should be OFF.