101
Instant cut power
supply
Repower on after voltage is
stable
1
E-041
Drive power
off
Drive power cut off
Check the power supply
3
E-043
Bus voltage
charging
failure
Hardware damage
Please note if there is relay
ON/OFF sound when drive
power on
06
0
E-060
Module
temperature
too high
1. long time running
with large load
2. environment
temperature too high
3. short circuit
between UVW
1. consider change the motor
capacity(mointor U0-02,
motor present torque)
decrease the load
2. good ventilation, check if
the fan is running when
module temperature U0-06
45
3. check the UVW wiring
1
E-061
Motor
temperature
too high
1. long time running
with large load
2. environment
temperature too high
1. decrease the load
2. good ventilation
2
E-062
Drive too
cold
Environment
temperature is too
low
The environment must up to
0
07
0
E-070
Current too
large
Not match the motor
code
Drive P0-33 must match the
motor code on the motor label
U, V, W wiring error
Check the UVW wiring
Encoder problem
1. Check encoder cable or
change it 2. Set servo to bb

Other manuals for Xinje DS3E Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xinje DS3E Series and is the answer not in the manual?

Xinje DS3E Series Specifications

General IconGeneral
BrandXinje
ModelDS3E Series
CategoryServo Drives
LanguageEnglish

Related product manuals