4. Auxiliary running parameters (Group P3)
Group P3: Auxiliary running parameters
Parameter Name Range
Minmum
unit
Factory
setting
Change
P3.00 Combination of
frequency input
0: VI+CI
1: VI-CI
2: External pulse+VI+
Increase/Decrease key
3: External pulse-VI-
Increase/Decrease key
4: External pulse+CI
5: External pulse -CI
6: RS485 +VI+Increase/Decrease
key
7: RS485-VI-Increase/Decrease
Key
8: RS485+CI+Increase/Decrease
key
9: RS485-CI-Increase/Decrease
key
10: RS485+CI+External pulse
11: RS485-CI-External pulse
12: RS485+VI+External pulse
13: RS485-VI-External pulse
14: VI+CI+Increase/Decrease key
+Digital setting
15: VI+CI-Increase/Decrease key
+Digital setting
16: MAX (VI, CI)
17: MIN (VI, CI)
18: MAX (VI, CI, PULSE)
19: MIN (VI, CI, PULSE)
20: VI, CI none-zero value is valid, VI
is priority
1 0 ×
P3.01 Parameter initialization
Lock
Lowest bit:
0: All parameters can be modified
1: Only P3.01 can be modified
2:Only P0.02 and P3.01 can be
modified
ten bit:
0: disabled
1: Restore to default setting
2: Clear fault record
1 00 ×
P3.02 Parameter copy 0:disabled
1:parameter upload
2:parameter download
Note:Function is still in developing
1 0 ×
P3.03 Auto energy-saving func- 0: disabled 1 0 ×