V5 series inverter
40
P3.25 Decerlate time 7 0.1~6000.0 0.1 10.0 ○
P3.26 Multi-frequency 1 Min frequency~max frequency 0.01Hz 5.00Hz ○
P3.27 Multi-frequency 2 Min frequency~max frequency 0.01Hz 10.00Hz ○
P3.28 Multi-frequency 3 Min frequency~max frequency 0.01Hz 20.00Hz ○
P3.29 Multi-frequency 4 Min frequency~max frequency 0.01Hz 30.00Hz ○
P3.30 Multi-frequency 5 Min frequency~max frequency 0.01Hz 40.00Hz ○
P3.31 Multi-frequency 6 Min frequency~max frequency 0.01Hz 45.00Hz ○
P3.32 Multi-frequency 7 Min frequency~max frequency 0.01Hz 50.00Hz ○
P3.33 Jump frequency 1 0.00~500.00Hz 0.01Hz 0.00Hz ×
P3.34 Range of jump frequency
1
0.00~30.00Hz 0.01Hz 0.00Hz ×
P3.35 Jump frequency 2 0.00~500.00Hz 0.01Hz 0.00Hz ×
P3.36 Range of jump frequency
2
0.00~30.00Hz 0.01Hz 0.00Hz ×
P3.37 Jump frequency 3 0.00~500.00Hz 0.01Hz 0.00Hz ×
P3.38 Range of jump frequency
3
0.00~30.00Hz 0.01Hz 0.00Hz ×
P3.39 Set running time 0~65.535K hour 0.001K 0.000K ○
P3.40 Accumulate running time 0~65.535K hour 0.001K 0.000K *
P3.41 Display parameters
selection 1
0000~FFFF
Lowest bit: b-09~b-12
Ten bit: b-13~b-16
Hundred bit: b-17~b-20
Thousand bit: b-21~b-24
1 0000 ○
P3.42 Display parameters
selection 2
0000~FFFF
Lowest bit: b-25~b-28
Ten bit: b-29~b-32
Hundred bit: b-33~b-36
Thousand bit: b-37~b-40
1 0000 ○
P3.43 Display parameters
selection 3
0000~4040
Ten bit, lowest bit: stop displayed
parameter selection
Thousand bit, hundred bit: run dis-
played parameter selection
1 0001 ○
P3.44 Display
coefficient without unit
0.1~60.0 0.1 1.0 ○
P3.45 JOG/REV shift control
mode
0: Jog running
1: reverse running
1 0 ×
5. Function parameters of terminal (Group P4)
Group P4: Function Parameters of Teriminal
Parameter Name Range
Minmum
unit
Factory
setting
Change
P4.00 Function selection of
input terminal X1
0: Control terminal is idle
1: Multi-speed control
terminal 1
2: Multi-speed control
1 1 ×

Table of Contents