EasyManuals Logo

Xtrails VESDA VLI User Manual

Default Icon
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #29 background imageLoading...
Page #29 background image
VESDA by Xtralis VESDA VLI Product Guide
www.xtralis.com 23
A+
A-
B-
Shield
Module 1 Module 2 Module 3
Module 5 Module 4
Shield
B+
A+
A-
B-
Shield
Shield
B+
A+
A-
B-
Shield
Shield
B+
A+
A-
B-
Shield
Shield
B+
A+
A-
B-
Shield
Shield
B+
(VLI-885)
Figure 3-11: Example closed loop VESDAnet network
The VLI-885 detector is shipped with the VESDAnet A and B terminals looped. Remove the A and B links prior
to connecting the detector to the VESDAnet. If the detector is not to be networked with other devices, then do
not remove the A and B links.
Note: For each VLI-885 detector connected on VESDAnet, ensure that the shield link wire (supplied) is
retained as shown by the dotted line in Figure 3-11. The link wires [A+ to B+] and [A- to B-] (not
shown in the figure but supplied for stand-alone operation) should be removed. On other VESDAnet
devices all the link wires are removed when connected on VESDAnet.
Shield
A-
A+
Shield
B-
B+
Figure 3-12: Closed loop for standalone detectors with VESDAnet capability
Note: Refer to the VESDA Communications Guide for further information.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xtrails VESDA VLI and is the answer not in the manual?

Xtrails VESDA VLI Specifications

General IconGeneral
BrandXtrails
ModelVESDA VLI
CategorySmoke Alarm
LanguageEnglish

Related product manuals