ICAM ILS-2 Product Guide ICAM by Xtralis
20 www.xtralis.com
Function Display Special Instructions
Set Channel 2 smoke detector
FIRE alarm threshold
FIRE 2 LED
flashes.
Please refer to Table 9-1.
Set SOUNDER On or Off If it sounds short beeps,
this signifies it is in the Off
setting.
If the buzzer sounds long
beeps, this signifies it is
On.
-
Set/Unset Alarm Latching
function
SMOKE
DETECTOR
FAULT LED
flashes.
Bargraph display
indicates alarm
latching status
(0 = Non Latching,
1 = Latching).
-
Calibrate flow sensors FAN FAULT LED
flashes.
CHANGE key must be pressed for at
least 2 seconds to initiate the flow
calibration process.
FAN and POWER LEDs flash to indicate
calibration in progress. Fan is temporarily
stopped as part of the calibration process.
The system will reset and revert to normal
operating mode when flow calibration is
completed.
Table 6-1: User Functions (continued...)
Pressing the SELECT key for longer than 1 second when the unit is unlocked will cause the unit to revert to
normal operating mode.
Momentarily pressing the SELECT or CHANGE key when the unit is locked (UNLOCK LED is off) causes the
unit to display the airflow on the bargraph. The display reverts back to the smoke level reading after
approximately four minutes.